B. Reference – Festo DeviceNet and FHPP

B-48

Festo P.BE-MTR-DCI-DN-EN en 1209a

Drive Data

FHPP

1026

1...8

Array

uint32

rw

Description

General Drive Data

Output Stage

Temp.

1026

1 (CI: 01h)

uint32

rw

Temperature of the output stage in °C. Value range: 0 ... 85

Output Stage

Max. Temp.

1026

2 (CI:02h)

uint32

rw

Maximum temperature for the output stage in °C. Fixed: 80 (0x0050)

Motor Rated

Current

1026

3 (CI: 03h)

uint32

rw

Motor rated current in [mA]
Value is automatically entered when an axis type (PNU 1005/4) is selected.

Current Limit 1026

4 (CI: 04h)

uint32

rw

Maximum motor current in 1/1000 of nominal current. Identical to PNU 1034.
Value range: 1...2000

Lower Current Limit 1026

5 (CI: 05h)

uint32

rw

= PNU1026,4 * (-1)

Device Control 1026

6 (CI: 06h)

uint32

rw

Setting the device controller (see PNU 125 / object 207Dh).
0: Control via HMI (control panel) or FCT, no control via field bus
1: Control via field bus – control interface (default)

Controller Serial

Number

1026

7 (CI: 07h)

uint32

rw

Serial number of the controller in format 0xDDMYYSSS:
DD (day):

8 Bit: 0x01...0x1F

M (month):

4 Bit: 0x1...0xC

YY (year):

8 bit: 0x00...0x63

SSS (serial no.):

12 bit: 0x001...0xFFF

Following error

(permitted

following error)

1026

8 (CI: 08h)

uint32

rw

Following error monitoring