5 input for external reference switch – Festo Электромотор MTR-DCI User Manual
Page 69
3. Installation
3-13
Festo P.BE-MTR-DCI-DN-EN en 1209a
3.5
Input for external reference switch
If you are not using a reference switch:
•
Seal the connection with the protective cap supplied
(ISK-M8).
When selecting the reference switch:
•
For the reference switch, use the correct “N.O.”
(normally-open) switch type in PNP configuration.
•
Use a reference switch with a screw-type lock (external
thread M8x1) at the end of the cable, or use the connect-
ing cable KM8-M8-... with a screw-type lock as an ad-
apter.
Use (e.g.) the following Festo proximity sensors:
–
magnetic proximity sensor SMT-8M-...
–
inductive proximity sensor SIEN-...-M8B-...
•
When selecting the sensor, note that the accuracy of the
switchover point of the sensor determines the accuracy of
the homing (reference) point.
M8x1 socket
Description
1
3
4
1
DC +24 V
DC + 24 V voltage output
(only for reference switch)
4
REF
Reference switch contact
3
GND
Ground
Tab. 3/7: REF connection (reference switch) on the MTR-DCI
The power supply for the reference switch (DC 24 V/Ground)
is provided via pin 1/3.