Homing (requires status 1.4 or 1.5), Commissioning 5-47 – Festo Электромотор MTR-DCI User Manual

Page 145

Advertising
background image

5. Commissioning

5-47

Festo P.BE-MTR-DCI-DN-EN en 1209a

4. Homing (requires status 1.4 or 1.5)

4.1

A positive edge at CPOS.B2 (HOM, Start homing) starts
the homing run. The start is confirmed with SPOS.B1
(Acknowledge start) as long as CPOS.B2 (HOM) is set.

4.2

Movement of the axis is shown with SPOS.B4 (MOV,
Axis is moving).

4.3

After successful homing, SPOS.B2 (MC, Motion
Complete) and SPOS.B7 (REF) are set.

Step/
Description

O data

I data

Byte

B7 B6 B5 B4 B3 B2 B1 B0 Byte

B7 B6 B5 B4 B3 B2 B1 B0

4.1 Start homing

Byte 1

OPM2 OPM1

LOCK

RESET BRAKE STOP

ENABL

Byte 1

OPM2 OPM1 LOCK

24VL

FAULT WARN OPEN ENABL

CCON

0

x

x

0

0

x

1

1

SCON

0

x

0

1

0

0

1

1

Byte 2

CLEAR TEACH JOGN

JOGP

HOM

START

HALT

Byte 2

REF

STILL

DEV

MOV TEACH

MC

ACK

HALT

CPOS

0

0

0

0

0

F

0

1

SPOS

0

0

0

0

0

0

1

1

4.2 Homing is in
progress

Byte 1

OPM2 OPM1

LOCK

RESET BRAKE STOP

ENABL

Byte 1

OPM2 OPM1 LOCK

24VL

FAULT WARN OPEN ENABL

CCON

0

x

x

0

0

x

1

1

SCON

0

x

0

1

0

0

1

1

Byte 2

CLEAR TEACH JOGN

JOGP

HOM

START

HALT

Byte 2

REF

STILL

DEV

MOV TEACH

MC

ACK

HALT

CPOS

0

0

0

0

0

1

0

1

SPOS

0

0

0

1

0

0

1

1

4.3 Homing con-
cluded

Byte 1

OPM2 OPM1

LOCK

RESET BRAKE STOP

ENABL

Byte 1

OPM2 OPM1 LOCK

24VL

FAULT WARN OPEN ENABL

CCON

0

x

x

0

0

x

1

1

SCON

0

x

0

1

0

0

1

1

Byte 2

CLEAR TEACH JOGN

JOGP

HOM

START

HALT

Byte 2

REF

STILL

DEV

MOV TEACH

MC

ACK

HALT

CPOS

0

0

0

0

0

0

0

1

SPOS

1

0

0

0

0

1

0

1

0: 0 signal

1: 1 signal;

x: not relevant (any);

F: Edge positive

Tab. 5/12: I/O data “Homing”

If there are faults during homing:
} Fault handling: see example 3, Tab. 5/11.

Advertising