6. Diagnosis and error display

6-10

Festo P.BE-MTR-DCI-DN-EN en 1209a

Fault

Possible cause

Remedy

DEVICENET INIT NO
PARAMETER ERROR

Essential bus parameters not set.
– MTR-DCI not on the bus.

Set bus parameters (see sec-
tion 5.2.7):
– MAC-ID
– Bit rate
– I/O Data length

HARDWARE ERROR

Device fault (EEPROM defective, or
user data damaged)

Contact Festo Service.

I2t-ERROR

Current monitoring i

2

t.

– The drive is blocked

Check the drive mechanism.

HOMING ERROR

Error during homing
– Homing run interrupted
– Homing switch defective

If necessary, check the function of
the homing switch.

It is essential that you repeat
homing.

LOAD-POWER-DOWN

Voltage monitoring
– Load voltage too low

MTR-DCI 32/42/52: U < 18 V
MTR-DCI 62: U < 34 V

– Voltage drops under load

Check the power supply:
– Power supply unit too weak?
– Supply line too long?

MOTOR STOP

Error during the positioning proced-
ure
– A positioning procedure has been

aborted on the control panel with
EMERG.STOP (button “Menu”).

Acknowledge the error on the
control panel with “Enter”

OVERHEATING

Overheating
(Operating temperature > 80 °C).
– Temperature of power stage too

high.

– Ambient temperature too high

Check:
– That the limits are complied

with (motor characteristic
curves),

– the mechanical parts e.g. for

stiffness.

If necessary, reduce the ambient
temperature.

PLEASE ENFORCE
HOMING RUN

When starting a position set:
– A valid homing process has not

yet been conducted.

– Due to a logic voltage failure the

reference position has been lost.

Carry out homing.