3. Installation

3-17

Festo P.BE-MTR-DCI-DN-EN en 1209a

3.6.2

Fieldbus cable

Note
Faulty installation and high transmission rates may cause
data transmission errors as a result of signal reflections
and attenuations.
Transmission errors can be caused by:

missing or incorrect terminating resistor

incorrect screened connection

branches

transmission over long distances

inappropriate cables

Observe the cable specifications! For information on the
cable type refer to the manual for your controller or to the
DeviceNet specification.

Note
If the MTR-DCI is mounted onto a moving part of a
machine, the Fieldbus cable on the moving part must be
provided with strain relief. Please observe also the relevant
regulations in EN 60204 part 1.

Use a shielded, twisted pair 4-wire cable as a fieldbus cable.
When using a Festo fieldbus a cable diameter of 5 ... 8 or
7 ... 10 mm is permitted.

Bus length

Exact specifications on the bus length can be found in the
next section and in the manuals for your control system.