2 fieldbus cable – Festo Электромотор MTR-DCI User Manual

Page 73

Advertising
background image

3. Installation

3-17

Festo P.BE-MTR-DCI-DN-EN en 1209a

3.6.2

Fieldbus cable

Note
Faulty installation and high transmission rates may cause
data transmission errors as a result of signal reflections
and attenuations.
Transmission errors can be caused by:

–

missing or incorrect terminating resistor

–

incorrect screened connection

–

branches

–

transmission over long distances

–

inappropriate cables

Observe the cable specifications! For information on the
cable type refer to the manual for your controller or to the
DeviceNet specification.

Note
If the MTR-DCI is mounted onto a moving part of a
machine, the Fieldbus cable on the moving part must be
provided with strain relief. Please observe also the relevant
regulations in EN 60204 part 1.

Use a shielded, twisted pair 4-wire cable as a fieldbus cable.
When using a Festo fieldbus a cable diameter of 5 ... 8 or
7 ... 10 mm is permitted.

Bus length

Exact specifications on the bus length can be found in the
next section and in the manuals for your control system.