4 parameterisation example – Festo Электромотор MTR-DCI User Manual

Page 181

Advertising
background image

5. Commissioning

5-83

Festo P.BE-MTR-DCI-DN-EN en 1209a

5.7.4

Parameterisation example

The following tables show an example of parameterising a
positioning task in the position set table via FPC (Festo Para-
meter Channel).

Step 1

Output status of the 8 bytes of FPC data:

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Reserved Subindex ReqID/ResID + PNU

Parameter value

O data

0x00

0x00

0x

00

0x00

0x00

0x00

0x00

0x00

I data

0x00

0x00

0x

00

0x00

0x00

0x00

0x00

0x00

Step 2

Write record number 1 with absolute positioning:
PNU 401, subindex 2 – modify parameter value, array, byte:
ReqID 12 (0xC) with value 0x00.

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Reserved Subindex ReqID/ResID + PNU

Parameter value

O data

0x00

0x

02

0x

C1

0x

91

Unused

Unused

Unused

0x

00

I data

0x00

0x

02

0x

C1

0x

91

0x00

0x00

0x00

0x

00

Step 3

After receiving the I-data with ResID 0xC send O-data with
ReqID = 0x0 and wait for I-data with ResID = 0x0:

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

Reserved Subindex ReqID/ResID + PNU

Parameter value

O data

0x00

0x02

0x

01

0x91

Unused

Unused

Unused

0x00

I data

0x00

0x02

0x

01

0x91

0x00

0x00

0x00

0x00