5. Commissioning

5-87

Festo P.BE-MTR-DCI-DN-EN en 1209a

5.8.1

Establish “ready to operate” status

T

Internal conditions

Actions of the user

T1

Drive has been switched on.
No faults are ascertained.

T2

Load voltage applied.
Fieldbus master is accepted as the higher-order
controller.

“Enable drive” = 1
CCON = xxx0.xxx

1

T3

“Stop” = 1
CCON = xxx0.xx

11

T4

“Stop” = 0
CCON = xxx0.xx

01

T5

“Enable drive” = 0
CCON = xxx0.xxx

0

T6

“Enable drive” = 0
CCON = xxx0.xxx

0

T7*

Fault detected.

T8

Reaction to fault is complete, drive is stationary.

T9

There is no longer a fault.
It was a serious fault.

“Acknowledge fault” = 0

→ 1

CCON = xxx0.

Pxxx

T10

There is no longer a fault.
It was a minor fault.

“Acknowledge fault” = 0

→ 1

CCON = xxx0.

Pxx1

T11

Fault still exists.

“Acknowledge fault” = 0

→ 1

CCON = xxx0.

Pxx1

Key: P = positive edge, N = negative edge, x = any