I/o data length – Festo Электромотор MTR-DCI User Manual
Page 120
5. Commissioning
5-22
Festo P.BE-MTR-DCI-DN-EN en 1209a
I/O data length
–
Possible data lengths:
–
8 bytes (for sequence control as per the FHPP
standard)
–
16 bytes (8 bytes for sequence control as per the
FHPP standard + an additional 8 bytes for parameter-
ising via FHPP FPC)
–
The default setting is an
invalid data length
(displayed on the control panel as “???”)
This ensures that the correct data length has to be
entered during commissioning or when replacing the unit.
Set the data length as follows:
1. Select [Settings] [Bus parameter] [I/O Datalength]
(see also section 4.5).
2. Press <Enter> to display the current setting.
3. Set the desired length with the arrow buttons.
The setting must agree with the configuration of the
DeviceNet master (see chapter 5.4.2).
4. Accept the setting with OK <Enter>.
The set data length becomes effective immediately and is
saved against power failure.
} Settings
Bus parameter
I/O Datalength
I/O Datalength
8 Byte I/O Data
ESC <Menu>
EDIT <-->
OK <Enter>