Festo Электромотор MTR-DCI User Manual

Page 169

Advertising
background image

5. Commissioning

5-71

Festo P.BE-MTR-DCI-DN-EN en 1209a

Sequence

1. The user specifies the desired nominal value (in % of the

rated motor torque) and the speed limit in his/her output
data.

2. With a rising edge on Start (CPOS.B1) the controller

accepts the nominal torque and begins applying force/
torque in the direction indicated by the nominal value's
sign.

Once this speed has been reached, the “Speed limit
reached” bit is set in the (status byte SDIR).

Once the nominal value has been reached, taking into
account the target window and the time window, the
“MC” signal is set. The motor current continues to be
controlled.

In the case of resistance, e.g. from a workpiece in the
traversing range, the drive pushes against the
obstruction with a defined force (see Fig. 5/8).

If the distance set in path/stroke monitoring (relative
to the start position) is exceeded, the bit “Stroke limit
reached” is set in the status byte SDIR. The drive is
braked with the emergency-stop ramp, is then held in
a controlled position (the current position), and the
MC signal is set.

Possible causes of faults:

Homing not carried out.

Axis is at the SW end position when the positioning task
starts.

Advertising