Festo Электромотор MTR-DCI User Manual

Page 169

Advertising
background image

5. Commissioning

5-71

Festo P.BE-MTR-DCI-DN-EN en 1209a

Sequence

1. The user specifies the desired nominal value (in % of the

rated motor torque) and the speed limit in his/her output
data.

2. With a rising edge on Start (CPOS.B1) the controller

accepts the nominal torque and begins applying force/
torque in the direction indicated by the nominal value's
sign.

–

Once this speed has been reached, the “Speed limit
reached” bit is set in the (status byte SDIR).

–

Once the nominal value has been reached, taking into
account the target window and the time window, the
“MC” signal is set. The motor current continues to be
controlled.

–

In the case of resistance, e.g. from a workpiece in the
traversing range, the drive pushes against the
obstruction with a defined force (see Fig. 5/8).

–

If the distance set in path/stroke monitoring (relative
to the start position) is exceeded, the bit “Stroke limit
reached” is set in the status byte SDIR. The drive is
braked with the emergency-stop ramp, is then held in
a controlled position (the current position), and the
MC signal is set.

Possible causes of faults:

–

Homing not carried out.

–

Axis is at the SW end position when the positioning task
starts.

Advertising