Homing
Attention! Motor moves.

ESC <Menu>
START <Enter>

Homing
V_sw = 20 mm/s
v_s0 = 10 mm/s

EMERG.STOP<Menu>

4. The control panel (type MTR-DCI-...-H2 only)

4-14

Festo P.BE-MTR-DCI-DN-EN en 1209a

DEMO.
STOP

Pressing <Enter> cancels the positioning run.
The current positioning set is executed before
the axis stops. On restart, the process begins
with the first positioning set

.

EMERG.
STOP

Pressing the <Menu> button cancels the current
positioning run (

> Fault MOTOR STOP).

4.4.3

[Positioning] [Homing]

Note

When performing a homing run, please also note the
explanation in chapter 5.2.

First set the parameters in the menu [Settings] [Homing
paramet.]. (see chapter 4.5.3.). Factory setting: Homing to
stop in negative direction.

To define the reference point through a homing run:

Start homing with START <Enter>.

The following information is displayed:

The search speed v_sw for moving to the reference point

The positioning speed v_s0 to the axis zero point v_0.

During the homing run, the axis slowly moves with reduced
search speed to the stop or reference switch and then
accepts this position as the reference point.