5. Commissioning

5-14

Festo P.BE-MTR-DCI-PB-EN en 1209a

Discontinuing homing

If necessary, homing can be discontinued with the <Menu>
button (EMERG STOP). If correct homing has already been
carried out, the previous homing point will retain its validity.

Error in the homing run

If a fault occurs during homing:

•

Acknowledge the error message with <Enter>.

•

If necessary, check the function of the reference switch.

•

Check the settings of the parameters.

•

If necessary, position the drive in Teach mode so that,
when viewed in terms of the search direction, it is

in front

of the stop or reference switch at the start.

•

Repeat the homing run.