Discontinuing homing, Error in the homing run – Festo Электромотор MTR-DCI User Manual

Page 102

Advertising
background image

5. Commissioning

5-14

Festo P.BE-MTR-DCI-PB-EN en 1209a

Discontinuing homing

If necessary, homing can be discontinued with the <Menu>
button (EMERG STOP). If correct homing has already been
carried out, the previous homing point will retain its validity.

Error in the homing run

If a fault occurs during homing:

Acknowledge the error message with <Enter>.

If necessary, check the function of the reference switch.

Check the settings of the parameters.

If necessary, position the drive in Teach mode so that,
when viewed in terms of the search direction, it is

in front

of the stop or reference switch at the start.

Repeat the homing run.