6. Diagnostics and fault display

6-13

Festo P.BE-MTR-DCI-PB-EN en 1209a

The faults are divided into logical groups according to the
fault numbers.

Group

Name

Comment

0

No fault active

1 ... 19

Execution fault

Examples: no homing, nominal position outside software end
positions, nominal value calculation not possible.
Although the system is OK, a user command cannot be ex-
ecuted. In most cases there is a fault in operation.
Source: sequence control, controller

20..29

Parameter fault

Example: software end positions outside the effective stroke.
A parameter lies within the limit values, allowing it to be writ-
ten by the user. During the recalculation by the controller,
it was found to be invalid in the context of the other paramet-
ers.
Note: invalid parameters are rejected by the parameter pro-
tocol and do not generate a fault in the controller.

30..49

Controller

Examples: positioning timeout, homing not successful, posi-
tion lag error too large, ...
The task could not be executed correctly. No hardware fault
could be detected. Source: controller

50..69

Initialisation

Fault when initialising the controller

70..79

Controller runtime

Controller runtime fault: undervoltage, checksum

80 ... 89

Reserved

90 ... 99

Reserved

100 ... 109

Motor runtime

Motor runtime: undervoltage, overtemperature, ...

110 ... 119

Reserved

Tab. 6/11: Overview of fault numbers