5. Commissioning
5-21
Festo P.BE-MTR-DCI-PB-EN en 1209a
5.2.7
Setting PROFIBUS addresses
Before commissioning on the PROFIBUS, you must set a valid
station number.
–
Valid station numbers: 0 ... 125.
–
The
invalid station number 255 is preset.
This is to make sure that a correct address is set during
commissioning or when replacing.
–
Addresses cannot be assigned by the master (the service
Set_Slave_Address is not supported).
Note
Station numbers may only be assigned once per fieldbus
master.
Set the station numbers as follows:
1. Select [Settings] [PB parameter] [PROFIBUS ADR]
(see also section 4.4).
2. The current address is displayed with <Enter>.
3. Set the desired address with the arrow buttons.
4. Accept the address with OK <Enter>.
The set address becomes effective immediately and is
saved against network failure.
} Settings
PB parameter
PROFIBUS ADR
PROFIBUS address
7
ESC <Menu>
EDIT <-->
SAVE <Enter>