B. Supplementary information

B-36

Festo P.BE-MTR-DCI-PB-EN en 1209a

Force mode

Stroke Limit

PNU

510

uint32

rw

Description

Maximum permitted stroke when Force mode is active. With Force mode active,
the distance between the actual position and the start position must not be more
than the amount specified in this parameter. In this way you can ensure that, if
Force mode is activated by mistake (e.g. when workpiece is missing), the axis will
not perform an uncontrolled movement. This parameter is evaluated in all con-
troller modes in which the position controller is not active when the status “oper-
ation enabled” is set.

The monitoring can be deactivated by setting the bit RCB1.B5.

Value range: 0...4,294,967,295 inc

CI access

60F6h

01h

uint32

rw

Min. Torque (min. permitted force/torque)

PNU

511

uint16

rw

Description

This value represents the lowest permissible torque (or force) of the motor. The
value is given in 1/1000 of the nominal torque (6076h / PNU 509).

Value range: 0...1000 (0x03E8)

CI access

60F6h

05h

uint16

rw

Max. Torque (max. permitted force/torque)

PNU

512

uint16

rw

Description

This value represents the highest permissible torque (or force) of the motor. The
value is given in 1/1000 of the nominal torque (6076h / PNU 509).

Value range: 0...1000 (0x03E8)

CI access

6072h

00h

uint16

rw