5. Commissioning

5-52

Festo P.BE-MTR-DCI-PB-EN en 1209a

2. Establishing “ready to operate” status –
Direct mode

Step/
Description

Control bytes

Status bytes

Byte

B7

B6

B5 B4

B3

B2 B1 B0

Byte

B7 B6 B5 B4 B3 B2 B1 B0

2.1 Basic status

(HMI device control =
off )

Byte 1

OPM2 OPM1

LOCK

RESET BRAKE STOP ENABL

Byte 1

OPM2 OPM1 LOCK

24VL

FAULT WARN OPEN ENABL

CCON 0

0

0

0

0

x

0

0

SCON 0

0

0

1

0

0

0

0

Byte 2

CLEAR TEACH JOGN

JOGP

HOM

START

HALT

Byte 2

REF

STILL

DEV

MOV TEACH

MC

ACK

HALT

CPOS x

0

0

0

0

0

0

0

SPOS 0

0

0

0

0

1

0

0

2.2 Disable device
control by FCT/HMI

Byte 1

OPM2 OPM1

LOCK

RESET BRAKE STOP ENABL

Byte 1

OPM2 OPM1 LOCK

24VL

FAULT WARN OPEN ENABL

CCON x

x

1

x

x

x

x

x

SCON x

x

0

x

x

x

x

x

Byte 2

CLEAR TEACH JOGN

JOGP

HOM

START

HALT

Byte 2

REF

STILL

DEV

MOV TEACH

MC

ACK

HALT

CPOS x

x

x

x

x

x

x

x

SPOS x

x

x

x

x

x

x

x

2.3 Enable drive,
enable operation

(Direct mode)

Byte 1

OPM2 OPM1

LOCK

RESET BRAKE STOP ENABL

Byte 1

OPM2 OPM1 LOCK

24VL

FAULT WARN OPEN ENABL

CCON

0

1

x

x

0

x

1

1

SCON

0

1

0

1

0

0

1

1

Byte 2

CLEAR TEACH JOGN

JOGP

HOM

START

HALT

Byte 2

REF

STILL

DEV

MOV TEACH

MC

ACK

HALT

CPOS x

0

0

0

0

0

0

1

SPOS 0

0

0

0

0

1

0

1

0: 0-signal;

1: 1-signal;

x: not relevant (any);

F: Edge positive

Tab. 5/10: Control and status bytes for “Establishing 'ready to operate' status –

Direct mode”

Description for 2. Establishing “ready to operate” status:

2.1

Basic status of the drive when the supply voltage is
switched on.

} Step 2.2 or 2.3

2.2

Disable device control by FCT/HMI.
Optionally, takeover of device control by FCT/HMI can
be disabled with CCON.B5 = 1 (LOCK).

} Step 2.3

2.3

Enable drive in Direct mode.

} Homing: example 4, Tab. 5/12.

If there are faults after switching on or after setting CCON.B0
(ENABLE):
} Fault handling: see example 3, Tab. 5/11.