5. Commissioning

5-65

Festo P.BE-MTR-DCI-PB-EN en 1209a

Overview of parameters involved (see also section B.1.12)

Parameters involved

Description

FCT

PNU

CI

Axis zero point offset

x

1010

607Ch

Homing method

x

1011

6098h

Homing speeds

x

1012

6099h

Homing required

1014

23F6h

Maximum homing torque

x

1015

23F7h

Start

CPOS.B2 = positive edge: Start homing

Feedback

SPOS.B1 = positive edge: Acknowledge start
SPOS.B7 = drive homed to reference point

Requirement

Device control by PLC/fieldbus
Controller must be in status “Operation enabled”
No active command for jogging

Tab. 5/18: Parameters involved in homing

Homing methods

1)

hex.

dec.

Description

17h

23

Search for reference switch in positive direction.

1Bh

27

Search for reference switch in negative direction.

EFh

-17

Search for negative stop. The point found is the reference position. As the
axis must not stand still at the stop, the axis zero point offset must be ≠ 0.

EEh

-18

Search for positive stop. The point found is the reference position. As the
axis must not stand still at the stop, the axis zero point offset must be ≠ 0.

1)

For detailed description of homing methods see section 5.2.2.

Tab. 5/19: Overview of homing methods