Diagnostic Memory Parameter (diagnostic memory parameters)
PNU
204
1...4
0...3
uint8
rw
Description
Configuration of the diagnostic memory.
Fault Type 204
1
0
Incoming and outgoing faults
1 (0x01): Record incoming and outgoing
*)
faults (default)
2 (0x02): Record only incoming faults
*) Outgoing fault = time when the fault was acknowledged (= reset).
Resolution 204
2
1
1 (0x01): Time stamp resolution 10 ms (default)
2 (0x02): Time stamp resolution 1 ms
Clear Memory 204
3
2
Deletes diagnostic memory by writing value = 1.
Read will always be answered with value = 1.
Number of Entries 204
4
3
Reads out the number of entries in the diagnostic memory.
CI access
20CCh
01h...04h
uint8
rw/ro
Device Error (device fault)
PNU
205
–
–
uint16
rw
Description
Reading or deleting the active device fault.
Read [bit 0...15]: see section 6.3, Tab. 6/7.
Write 0 (0x0000): deletes all faults.
CI access
2FF1h
00h
uint16
rw