Festo Электромотор MTR-DCI User Manual

Page 35

Advertising
background image

1. System overview

1-15

Festo P.BE-MTR-DCI-PB-EN en 1209a

1.5.3

Reference travel

In the case of drives with incremental measuring system, a
reference travel must always be carried out after the drive is
switched on. This is defined drive-specifically with the para-
meter “Reference travel required” (PNU 1014, CI 23F6h).

The following reference travel modes are permissible:

Search for stop in a negative direction

Search for stop in a positive direction

Search for reference switch in a positive direction

Search for reference switch in a negative direction (de-
fault).

In order to search for the reference point and for positioning
the drive in the axis zero point, you can set two different
speeds.

Reference travel sequence:

1. Search for the reference point in accordance with the con-

figured method

2. Move from reference point to axis zero point AZ (axis zero

point offset)

3. Set at axis zero point:

Current position = 0 – project zero point PZ offset

After successful reference travel, the drive stands at the axis
zero point AZ. On initial start-up or following a change of ref-
erence travel method the axis zero offset = 0; after reference
travel the drive is then positioned at the reference point REF.