6. Diagnostics and fault display

6-16

Festo P.BE-MTR-DCI-PB-EN en 1209a

Station status 1

Bit 3 is especially of interest with station status 1. If this bit is
set, it is useful to evaluate the device-related diagnosis.

Station status 1

Bit

Meaning

Explanation

0

Diag.Station_Non_Existent

MTR-DCI no longer/not yet addressable.
Possible causes:

Operating voltage not applied

Data transmission line interrupted

Fault in data transmission line

1

Diag.Station_Not_Ready

MTR-DCI is not yet ready for data exchange.

2

Diag.Cfg_Fault

The configuration data received from the master are not
the same as those ascertained by the MTR-DCI.

3

Diag.Ext_Diag

A device-related diagnosis exists.

1)

4

Diag.Not_Supported

1 = The MTR-DCI does not support the function re-

quested.

5

Diag.Invalid_Slave_Response

Always 0 (always reset to 0 by the MTR-DCI).

2)

6

Diag.Prm_Fault

Last parameter assignment telegram faulty

7

Diag.Master_Lock

Access by a different master (is set by the master)

1)

Is set by the MTR-DCI when a new fault occurs (new fault message).

2)

Is set to 1 in the DP master when the response sent by the slave cannot be interpreted.

Tab. 6/13: Diagnostic bits of station status 1