5. Commissioning

5-47

Festo P.BE-MTR-DCI-PB-EN en 1209a

Status byte 2 (SPOS)

Bit

EN

Description

B0
HALT

Halt

= 0: Halt is active
= 1: Halt is not active, axis can be moved

B1
ACK

Acknowledge start

= 0: Ready for start (homing, jog)
= 1: Start carried out (homing, jog)

B2
MC

Motion Complete

= 0: Positioning task active
= 1: Positioning task completed, possibly with fault
Note: MC is first set after switching on (status “Drive
blocked”)

B3
TEACH

Acknowledge

teaching

= 0: Ready for teaching
= 1: Teaching carried out, actual value transferred

B4
MOV

Axis is

moving

= 0: Speed of the axis < limit value
= 1: Speed of the axis >= limit value

B5
DEV

Deviation warning

= 0: No position lag error
= 1: Position lag error active

B6
STILL

Stand

still warning

= 0: After MC, axis remains in tolerance window
= 1: After MC, axis is outside tolerance window

B7
REF

Axis is

referenced

= 0: Homing must be carried out
= 1: Home information exist, homing does not need to be

carried out