5. Commissioning
5-47
Festo P.BE-MTR-DCI-PB-EN en 1209a
Status byte 2 (SPOS)
Bit
EN
Description
B0
HALT
Halt
= 0: Halt is active
= 1: Halt is not active, axis can be moved
B1
ACK
Acknowledge start
= 0: Ready for start (homing, jog)
= 1: Start carried out (homing, jog)
B2
MC
Motion Complete
= 0: Positioning task active
= 1: Positioning task completed, possibly with fault
Note: MC is first set after switching on (status “Drive
blocked”)
B3
TEACH
Acknowledge
teaching
= 0: Ready for teaching
= 1: Teaching carried out, actual value transferred
B4
MOV
Axis is
moving
= 0: Speed of the axis < limit value
= 1: Speed of the axis >= limit value
B5
DEV
Deviation warning
= 0: No position lag error
= 1: Position lag error active
B6
STILL
Stand
still warning
= 0: After MC, axis remains in tolerance window
= 1: After MC, axis is outside tolerance window
B7
REF
Axis is
referenced
= 0: Homing must be carried out
= 1: Home information exist, homing does not need to be
carried out