6. Diagnostics and fault display

6-10

Festo P.BE-MTR-DCI-PB-EN en 1209a

Fault

Possible cause

HARDWARE ERROR

Device error, e.g. EEPROM defective.
• Contact Festo Service.

HOMING ERROR

Fault during homing
Possible causes:

Homing interrupted

Reference switch defective

• If necessary, check the function of the reference switch.
• In all cases, be sure to repeat the homing run.

i

2

t-ERROR

Current monitoring i

2

t.

Possible cause:
The drive is blocked.
• Check the drive's mechanical components.

PLEASE ENFORCE
HOMING RUN!

When starting a position set record.
Possible causes:

Valid homing has not yet been carried out.

The homing (reference) position has been lost due to logic voltage
failure.

• You must carry out a homing run in all cases.

MOTOR STOP

Fault during the positioning procedure
Possible cause:
The positioning procedure was interrupted on the control panel with EMER-
G.STOP (<Menu> button).
• Acknowledge the fault on the control panel with <Enter>

OVERHEATING

Overheating (operating temperature > 80 °C)
Possible cause:

Motor overloaded

Ambient temperature too high

• Check:

That the limits are being observed (motor characteristic curves)

The mechanical parts e.g. for stiffness

• If necessary, reduce the ambient temperature.