3-16

Festo P.BE-MTR-DCI-PB-EN en 1209a

3.6.1

Fieldbus cable

Note
If installation has not been carried out correctly and if high
baud rates are used, data transmission errors may occur
as a result of signal reflections and attenuations.
Causes of the transmission faults may be:

– Missing or incorrect terminating resistor

– Incorrect screening/shield connection

– Branches

– Transmission over long distances

– Unsuitable cables

Observe the cable specifications. Refer to your controller
manual for information on the type of cable to be used.

Note
If the MTR-DCI is mounted onto a moving part of a ma-
chine, the fieldbus cable on the moving part must be pro-
vided with strain relief. Please observe also the relevant
regulations in EN 60204 part 1.

Use a twisted, screened 2-core cable for the fieldbus cable in
accordance with PROFIBUS specifications (EN 50170, cable
type A):

Surge impedance:

135-165 ohm (3-20 MHz)

Capacitance per unit length:

< 30 nF/km

Loop resistance:

< 110 Ohm/km

Core diameter:

> 0.64 mm

Core cross-section:

> 0.34 mm

2

Bus length

Exact specifications on the bus length can be found in the
next section and in the manuals for your control system.