3. Installation

3-10

Festo P.BE-MTR-DCI-PB-EN en 1209a

3.3.3

Separate supply with load and logic voltage

With separate supply, the load voltage can be switched off
(e.g. in the case of EMERGENCY-STOP), with logic voltage
continuing to be applied and the controller remaining func-
tional, retaining its reference position.

Supply with

load voltage is as above (see 3.3.2).

The

logic voltage, however, is supplied via the fieldbus

adapter FBA-... (see Accessories chapter) :

1

Fieldbus
connection

2

Continuation of
the fieldbus or
terminating
resistor

3

Supply of
separate logic
voltage

1

2 3

For the pin allocation and connection specification, see the
installation manual of the fieldbus adapter.
If connection

3 is not used: apply a protective cap to main-

tain the IP protection class (see A.2).

Switch-on sequence

Do

not switch on the logic voltage after the load voltage,

since this may cause the MTR-DCI to switch off and back on
again (= reset).

Logic voltage failure

If the logic voltage fails, the controller will switch off.
For MTR-DCI-42/52/62: if the load voltage is still active,
it will switch back on but will lose its reference position
(= reset).