B. Supplementary information

B-80

Festo P.BE-MTR-DCI-PB-EN en 1209a

Status Word

CI access

6041h

00h

Var

uint16

r

Description

For reading the current controller/regulator status.
For typical values see Tab. B/17. For description see Tab. B/18.

Bit

Value

Comment

0x0000

NOT_READY_TO_SWITCH_ON
Preinitialisation status

0x0021

READY_TO_SWITCH_ON
Status after initialisation

0x0027

SWITCHED_ON + OPERATION_ENABLE
Power electronics and positioning are enabled

3

0x000F

FAULT – there is a fault
(screen display at bit 3: 0x0008)

4

0x0010

VOLTAGE_DISABLED
Status

1: output stage OFF
0: output stage ON

(screen display at bit 4: 0x0010)

9

0x0200

1: enable logic, 0: disable logic

10

0x0400

1: TARGET_REACHED/MOTION_COMPLETE
0: MOTION_NOT_COMPLETE.
(screen display at bit 10: 0x0400)

11

0x0800

1: Internal limit active
0: Internal limit not active
I

2

t is active

(screen display at bit 11: 0x0800)

12

0x1000

1: New positioning task has been accepted or
homing run has finished.

13

0x2000

1: HOMING_ERROR
0: HOMING_NO_ERROR
(screen display at bit 13: 0x2000)

Tab. B/17: Typical values for Status Word