4.2 Control Modes

4-13

4

„

Details

Use the following procedure to perform operations in the torque reference output mode.

1. Set the motion fixed parameters according to the user’s machine.

Table 4.2 shows the related parameters when the torque reference output mode is used.

* 1. Valid only with an SVB-01 Module.
* 2. Valid only with an SVA-02A Module.

2. Set the motion parameters.

3. Select the Torque Reference Output Mode (TCON) (bit 1 of OW††00).

Table 4.2 Examples of Fixed Parameters

No.

Name

Setting Range

Meaning

Setting Example

7

Rated Motor Speed
Setting

1 to 32000

Rated motor speed

3000 r/min

8

Number of Feedback
Pulses per Motor Rotation

4 to 65532

Number of pulses
before multiplica-
tion

2048 pulses/rev

9

D/A Output Voltage at
100% Speed

0.001 to 10.000

1 = 1 V

6.000 V

Feedback Pulses per
Motor Rotation (for High-
resolution)

*1

4 to 2147483647 1 = 1 pulse/rev

2048 pulses/rev

10 D/A Output Voltage at

100% Torque Limit

*2

0.001 to 10.000

0.001 = 0.001 V
1 = 1 V

3.000 V

Table 4.3 Examples of Setting Parameters

Name

Register No.

Meaning

Setting Example

Torque Reference
Setting (TREF)

OW††1B

Sets the torque reference
value at 0.01%.

5000
(50.00%)

Speed Limit Setting
(NLIM)

OW††1C

Sets the speed limit
value at 0.01%.

5000
(50.00%)

0

1. Set the motion fixed parameters.

2. Set the motion setting parameters.

3. Set the torque reference output mode (TCON).

4. Set the RUN command (RUN) to ON.

RUN

TCON

5. Set the torque reference output mode to OFF.

Torque speed

Torque reference

Output the torque reference and speed limit reference.

(%)

: System execution

: User settings

Time (t)