Plc function specifications – Yaskawa MP920 User's Manual Design User Manual

Page 50

Advertising
background image

2 MP920 Specifications and System Configuration

2.1.3 Function Lists

2-24

„

PLC Function Specifications

Table 2.22 lists the PLC function specifications.

Commands

Axis Move Commands: 8 commands
MOV, MVS, MCW, MCC, ZRN, SKP, MVT, EXM
Basic Control Commands: 6 commands
ABS, INC, POS, PLN, MVM, PLD
Speed and Acceleration/Deceleration Commands: 8 commands
ACC, DCC, SCC, VEL, IAC, IDC, IFP, FMX
High-level Control Commands: 4 commands
PFN, INP, SNG, UFC
Control Commands: 10 commands
MSEE, TIM, IOW, END, RET, EOX, IF ELSE IEND, WHILE
WEND, PFORK JOINTO PJOINT, SFORK JOINTO SJOINT
Math and Sequence Control Commands: 36 commands
=, +, -, *, /, MOD, |, ^, &, !, (), S{}, R{}, SIN, COS, TAN,
ASN, ACS, ATN, SQRT, BIN, BCD, = =, < >, >, <, >=, <=,
SFR, SFL, BLK, CLR

Table 2.21 MP920 Motion Control Function Specifications (cont’d)

Item

Specification

Table 2.22 PLC Function Specifications

Item

Specifications

Program Capacity

Equivalent to 4 Ksteps (varies according to amount of motion program used; 20 Ksteps max.)

Control Method

Sequence: High-speed and low-speed scan methods

Programming
Language

CP language
Ladder logic diagram: Relay circuit
Text-type language: Numeric operations, logic operations, etc.

Scanning

Two scan levels: High-speed scan and low-speed scan
High-speed scan time setting: 0.4 to 300 ms (0.1 ms units)
Low-speed scan time setting: 1.0 to 300 ms (0.1 ms units)

User Drawings,
Functions and
Motion Programs

Start drawings (DWG.A):

64 drawings max. Up to three hierarchical drawing levels

High-speed scan process drawings (DWG.H):200 drawings max. Up to three hierarchical drawing levels
Low-speed scan process drawings (DWG.L): 500 drawings max. Up to three hierarchical drawing levels
Interrupt processing drawings (DWG.I):

64 drawings max. Up to three hierarchical drawing levels

Number of steps:

Up to 500 steps per drawing

User functions:

Up to 500 functions

Motion programs:

Up to 256

Revision history of drawings and motion programs
Security function for drawings and motion programs

Data Memory

Common data (M) registers:

32 kwords

System (S) registers:

1 kwords

Drawing local (D) registers:

Up to 16 kwords per drawing

Drawing constant (#) registers: Up to 16 kwords per drawing
Input (I) registers:

5 kwords (including internal input registers)

Output (O) registers:

5 kwords (including internal output registers)

Constant (C) registers:

16 kwords

Trace Memory

Data trace:

128 kwords (32 kwords

× 4 groups), 16 points defined

Failure trace: 4 kwords, 64 items defined

Memory Backup

Program memory: CMOS battery backup

Advertising