4 Motion Control

4.3.1 Prerequisites for Position Control

4-36

2. Reading Position Buffers

a) Set the Position Buffer Access Number (OL††38)(1 to 256).

b) Set the Position Buffer Read (OB††21F) in the Motion Command Control Flags to

ON. After two scans, the position data specified in Position Buffer Read Data
(IL††28) will be stored.

1. Position buffers can be used only when motion commands are used in the position control mode.

2. The position data specified in the position buffers are absolute position references.

The data in the position buffers is deleted by turning OFF the power and resetting the CPU Module
Master. Be sure to set the data when the power is turned ON, or before using the position buffers.

Using the Position Buffers as Position References

1. Set bit 12 of the RUN Command Settings (OW††01) to ON.
2. Set a position buffer number 1 to 256 in place of the position reference in the Position

Reference Setting (OL††12).

In this way, the data for the position buffer number specified in OL††12 functions as the
position reference.

256

CPU Module

93

543210

OW

21

OL

38

IL

28

1

2

3

1

2

3

256

1

2

3

256

1

2

3

256

93

543210

.

.

.

SVA Module

Axis 2

Axis 3

Axis 4

Axis 1 position buffers

INFO

IMPORTANT

1

This value will be
the position
reference.

OL

12

12345

OB

01C

OW

01

Position buffer number

Position buffers