Prohibited, Built-in fuses – Yaskawa MP920 User's Manual Design User Manual

Page 203

Advertising
background image

5 Modules

5.1.2 PS-01 Module

5-8

„

Built-in Fuses

The PS-01 Module has a built-in fuse to prevent the burning of the Module resulting from
the following causes.

• External causes:For example, if a PS-01 Module external power supply terminal is sub-

jected to overvoltage.

• Internal causes:For example, if a wire chip or other foreign wiring matter is left in the

PS-01 Module causing a short-circuit failure in an internal circuit.

If the PS-01 Module built-in fuse is blown, the POWER indicator on the front panel of the
PS-01 Module will turn OFF. After eliminating the cause of the blown fuse, replace the PS-
01 Module.

• The customer must not replace any built-in fuses.

If the customer replaces a built-in fuse, the PS-01 Module may malfunction or break down.
The built-in fuse must always be replaced by Yaskawa service staff.

FG

SG

FG

SG

AC

FG

SG

AC

AC

AC

AC

AC

PS-01 Module external
wiring terminals

Internal panel ground
wire (1.5 to 2.5 mm

2

)

Control panel casing

Ground terminal (E)

External panel ground wire (8 mm

2

)

Ground pole (ground resistance of 100

Ω or less)

Internal panel ground
wire (1.5 to 2.5 mm

2

)

Internal panel ground
wire (1.5 to 2.5 mm

2

)

PS-01 Module external
wiring terminals

PS-01 Module external
wiring terminals

PROHIBITED

Advertising