Dip switch (sw4), 215if port (cn1) – Yaskawa MP920 User's Manual Design User Manual

Page 322

Advertising
background image

5.6 Communications Modules

5-127

5

„

DIP Switch (SW4)

The SW4 is used to set the network number of the 215IF transmission. Set a network num-
ber between 1 and 254. The SW4 is valid only when the INIT of SW3 is set to ON.

All the pins of SW4 are set by default to OFF (to the right).

„

215IF Port (CN1)

Pins

Name

Setting

Operation

NET A0

NETWORK
ADDRESS 0

ON

See the table below.

OFF

NET A1

NETWORK
ADDRESS 1

ON

OFF

NET A2

NETWORK
ADDRESS 2

ON

OFF

NET A3

NETWORK
ADDRESS 3

ON

OFF

NET A4

NETWORK
ADDRESS 4

ON

OFF

NET A5

NETWORK
ADDRESS 5

ON

OFF

NET A6

NETWORK
ADDRESS 6

ON

OFF

NET A7

NETWORK
ADDRESS 7

ON

OFF

Network Number

1

2

3

···

254

A0

ON

OFF

ON

···

OFF

A1

OFF

ON

ON

···

ON

A2

OFF

OFF

OFF

···

ON

A3

OFF

OFF

OFF

···

ON

A4

OFF

OFF

OFF

···

ON

A5

OFF

OFF

OFF

···

ON

A6

OFF

OFF

OFF

···

ON

A7

OFF

OFF

OFF

···

ON

The CN1 is used for connection between 215IF Modules.
No standard cable available.

SW4

NET A0
NET A1
NET A2
NET A3
NET A4
NET A5
NET A6
NET A7

ON

OFF

ON

Advertising