Dip switch (sw4), 215if port (cn1) – Yaskawa MP920 User's Manual Design User Manual
Page 322

5.6 Communications Modules
5-127
5
DIP Switch (SW4)
The SW4 is used to set the network number of the 215IF transmission. Set a network num-
ber between 1 and 254. The SW4 is valid only when the INIT of SW3 is set to ON.
All the pins of SW4 are set by default to OFF (to the right).
215IF Port (CN1)
Pins
Name
Setting
Operation
NET A0
NETWORK
ADDRESS 0
ON
See the table below.
OFF
NET A1
NETWORK
ADDRESS 1
ON
OFF
NET A2
NETWORK
ADDRESS 2
ON
OFF
NET A3
NETWORK
ADDRESS 3
ON
OFF
NET A4
NETWORK
ADDRESS 4
ON
OFF
NET A5
NETWORK
ADDRESS 5
ON
OFF
NET A6
NETWORK
ADDRESS 6
ON
OFF
NET A7
NETWORK
ADDRESS 7
ON
OFF
Network Number
1
2
3
···
254
A0
ON
OFF
ON
···
OFF
A1
OFF
ON
ON
···
ON
A2
OFF
OFF
OFF
···
ON
A3
OFF
OFF
OFF
···
ON
A4
OFF
OFF
OFF
···
ON
A5
OFF
OFF
OFF
···
ON
A6
OFF
OFF
OFF
···
ON
A7
OFF
OFF
OFF
···
ON
The CN1 is used for connection between 215IF Modules.
No standard cable available.
SW4
NET A0
NET A1
NET A2
NET A3
NET A4
NET A5
NET A6
NET A7
ON
OFF
ON