12.2 System Errors

12-9

12

12.2.4

System Register Configuration

„

System Status

System status indicates the operating status and error details for the system. System status
details are used to determine whether hardware or software is the cause of an error.

Table 12.1 System Status List

Name

Register

No.

Contents

Reserved for
the System

SW00030 to
SW00039

(Not used)

CPU Status

SW00040

SB000400

READY

1: Normal,
0: Communications/Self-diagnosis error

SB000401

RUN

1: Running, 0: Stopped

SB000402

ALARM

1: Alarm, 0: Normal

SB000403

ERROR

1: Error, 0: Normal

SB000404

RESUME

1: Continued startup operation
0: New startup operation

SB000405

Start status

1: Restoration from power interruption
0: Ordinary restoration

SB000406

Reserved by system.

(Not used)

SB000407

WEN

1: WRITE enabled, 0: WRITE disabled

SB000408

Reserved by system.

SB000409

MASTER

1: Control system CPU, 0: Standby system

SB00040A

Reserved by system.

(Not used)

SB00040B

SB00040C

SB00040D

SB00040E

Operation stop request

1: STOP selection, 0: RUN selection

SB00040F

Reserved by system.

(Not used)

CPU Error
Status

SW00041

SB000410

Serious failure

1: WDGE, undefined command
See SW00050 for more details.

SB000411

Program memory error

1: Program memory error

SB000412

Calendar IC error

1: Calendar IC error

SB000413

Reserved by system.

(Not used)

SB000414

SB000415

SB000416

SB000417

SB000418

User operation error

1: User operation error

SB000419

I/O error

1: I/O error

SB00041A to
SB00041F

Reserved by system.

(Not used)