5 Modules
5.4.1 AI-01 Analog Input Module
5-60
Voltage Mode: 0 to 10 V, Current Mode: 0 to 20 mA
AI-01 Module Allocations
Channels for the AI-01 Module are allocated according to the following procedure.
1. Click the button on the right side of the Module field in the applicable slot number
column (04 in the above example) in the Module Definition Window. Click AI-01 and
set the starting I/O register. Double-click the slot number, and the AI-01 Configuration
Window will be displayed.
2. Set the applicable values in the In Range, REG No., and SCAN columns in the AI-01
Configuration Window. Set the register number to a value within the range specified by
32767
31276
10 V
(20 mA)
10.5 V
(21 mA)
0 V
0
Input register
Analog input