5.3 I/O Modules
5-17
5
External Input Connector
Connector Specifications
The following table shows the specifications of the connectors used to connect the DI-01
Module.
The external input Connector is used to connect a DI-01 Module to
external input signal terminals.
Use the following standard cable for this connector.
• JEPMC-W6060-
Number of input points: 64 points (32 points
× 2)
Input type: Combined sourcing/sinking
Name
Connector
Name
Number
of Pins
Connector
Cable
On Module
On Cable
Manufacturer
External Input
Signal
Connector 1
CN1
50
10250-52A2JL
• Connector body:
10150-3000VE
• Shell:
10350-52A0-008
(Screw lock)
10350-52F0-008
(One-touch lock)
3M
JEPMC-W6060-
External Input
Signal
Connector 2
CN2
50
10250-52A2JL
• Connector body:
10150-3000VE
• Shell:
10350-52A0-008
(Screw lock)
10350-52F0-008
(One-touch lock)
3M
JEPMC-W6060-