5.5.3 MECHATROLINK Interface Module (SVB-01)

5-98

Normal
operation

One of Servo Module numbers 1 to 16 will be dis-
played. The Servo Module is operating normally
and there is no error and alarm.

Serious fault

A two-digit error code appears following F
Examples:
F

→ 0 → 1: Watchdog timeout error

F

→ 4 → 1: ROM diagnostic error

F

→ 4 → 2: RAM diagnostic error

F

→ 4 → 3: Shared memory diagnostic error

F

→ 4 → 8: Illegal general instruction interrupt

F

→ 4 → 9: Illegal slot instruction interrupt

F

→ 5 → 0: CPU address error interrupt

F

→ 5 → 2: User break interrupt

F

→ 5 → 3: Trap instruction interrupt

F

→ 5 → 5: CERF initialization error

F

→ 5 → 8: TLB mistake exception interrupt

F

→ 5 → 9: TLB mistake exception interrupt

F

→ 6 → 0: TLB invalid exception interrupt

F

→ 6 → 1: TLB invalid exception interrupt

F

→ 6 → 2: Initialization page writing exception

interrupt

F

→ 6 → 3: TLB protection exception interrupt

F

→ 6 → 4: TLB protection exception interrupt

Alarm

One of the following occurs in one of the axes 1 to 14.

1. Motion setting parameter setting error

(See IB……001.)

2. Alarm occurrence (See IL……22.)
3. Motion command abnormal end

(When IB……155 = ON)

Error

The following error occurs in one of the axes 1 to 14.
Motion fixed parameter setting error
(See IB……002.)