3.3 Power Failures

3-9

3

3.3

Power Failures

This section explains the processing when an MP920 power failure occurs.

3.3.1

Power Failure Detection

Table 3.3 shows the start methods used when an MP920 power failure occurs.

The MP920 can select two types of startup: Continuous operation and new operation. The
selection of continuous operation or new operation is made on the MPE720 System Defini-
tion Window.

For details on the MPE720 operation method, refer to the Machine Controller MP900/
MP2000 Series MPE720 Software for Programming Device User’s Manual

(SIEPC8807005).

* Ns (power loss decision time) is defined on the MPE720 System Defini-

tion Window.

Table 3.3 MP920 Start Modes

Length of

Power Failure

Continuous Operation/

New Operation

Start Method

0 to 20 ms

Operations continue.

20 ms to Ns*
(Power loss)

When continuous operation
is selected

After the CPU is reset, no self-diagnosis is
performed, and operations continue.

When new operation is
selected

After the CPU is reset, self-diagnosis is per-
formed, and the new operation starts.

Ns* or more

When continuous operation
is selected

After the CPU is reset, no self-diagnosis is
performed, and operations continue.

When new operation is
selected

After the CPU is reset, self-diagnosis is per-
formed, and the new operation starts.