General Specifications of the MP920 Modules

Table 2.1 lists the general specifications of the MP920 Modules.

Table 2.1 General Specifications of the MP920 Modules

Item

Specifications

Environmental
Conditions

Ambient Operating
Temperature

0 to 55

°C

Storage Temperature

-25 to 85

°C

Ambient Operating
Humidity

30% to 95% RH (with no condensation)

Ambient Storage
Humidity

5% to 95% RH (with no condensation)

Pollution Level

Pollution level 1 (conforming to JIS B 3501)

Corrosive Gas

There must be no combustible or corrosive gas.

Operating Altitude

2,000 m above sea level or lower

Electrical
Operating
Conditions

Noise Resistance

Conforming to JIS B 3502:
1,500 V (p-p) in either normal or common modes
with a pulse width of 100 ns/11

µs and a rise time of

1 ns (tested with impulse noise simulator)

Mechanical
Operating
Conditions

Vibration Resistance

Conforming to JIS B 3502:
10 to 57 Hz with single-amplitude of 0.075 mm
57 to 150 Hz with fixed acceleration of 9.8 m/s

2

(1G)
10 sweeps each in X, Y, and Z directions
(sweep time: 1 octave/min)

Shock Resistance

Conforming to JIS B 3502:
Peak acceleration of 147 m/s

2

(15G) twice for 11 ms

each in the X, Y, and Z directions

Installation
Requirements

Ground

Ground to 100

Ω max.

Cooling Method

Natural cooling