Rotary switches, Dip switch (sw3) – Yaskawa MP920 User's Manual Design User Manual

Page 321

Advertising
background image

5 Modules

5.6.3 215IF Communications Module (215IF)

5-126

„

Rotary Switches

The SW1 and SW2 are used to set the station address on the 215IF transmission. The SW1
sets the 1s digit (

×1) and the SW2 sets the 10s digit (×10). Set a station address between 1

and 64. The SW1 and SW2 are valid only when the INIT of SW3 is set to ON.

„

DIP Switch (SW3)

The SW3 is used to set the operation mode such as transmission speed and self-diagnosis.

All the pins of SW3 are set by default to OFF (to the right).

„

INIT Pin of DIP Switch SW3

When the power is turned ON with the INIT pin set to ON, the 215IF Module executes message com-
munications according to the station addresses set by SW1 and SW2, the transmission speed set by
BRS0 and BRS1 of SW3, and the network address set by SW4. In this case, the link communication is
not executed and the relay function is disabled.
When the power is turned ON with the INIT pin set to OFF, the 215IF Module executes the link com-
munications and message communications according to the settings in the Module Condiguration Def-
inition Window of the MPE720. In this case, the settings of SW1, SW2, BRS0 and BRS1 of SW3, and
SW4 will be ignored.
To perform engineerings such as programming and register display on the MPE720 using the 215IF
Module when no module configuration definition is set, set the INIT pin to ON. Set the INIT pin to
ON only when forcibly communicating with the MPE720 such as when the CPU memory is cleared.

Indicator

Name

Setting

Function

ADRS

× 1

ADDRESS

× 1

0 to 6

Sets the station address 1s
digit.

ADRS

× 10

ADDRESS

×

10

0 to 6

Sets the station address 10s
digit.

SW1

SW2

ADRS
X1

ADRS
X10

Pins

Name

Setting

Operation

BRS0

Baud Rate
Select 0

ON

Transmission speed setting
(Valid only when the INIT is set to ON)

OFF

Transmission
speed (bps)

4M

2M

1M

BRS1

Baud Rate
Select 1

ON

BRS0

ON OFF ON OFF

OFF

BRS1

ON ON OFF OFF

INIT

INITIAL

ON

SW1, SW2, and BRS0 and BRS1 of SW3 are
valid.

OFF

Depends on the CPU transmission parameter set-
ting (software setting).

TEST

TEST

ON

Offline self-diagnosis mode

OFF

Normal operation mode

ON

SW3

ON

OFF

BRS0
BRS1
INIT
TEST

INFO