3 basic settings, 4 optimising the control mode, Basic settings – Lenze 8400 motec User Manual

Page 125: Optimising the control mode, 5motor control (mctrl)

Advertising
background image

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

125

5

Motor control (MCTRL)

5.8

Sensorless vector control (SLVC)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.8.3

Basic settings

The following "Initial commissioning steps" must be performed to commission the sensorless vector

control:

Tip!
We recommend to use the flying restart function for connecting/synchronising the inverter

to an already rotating drive system.

Flying restart function

( 148)

Parameterisable additional functions are described correspondingly in the chapter

"

Parameterisable additional functions

".

( 145)

5.8.4

Optimising the control mode

5.8.4.1

Optimising the starting performance after a controller enable

After the controller is enabled, a time delay is cause during the start due to the magnetisation of the

motor. If this delay cannot be tolerated for specific applications, the motor must always be operated

in an energised condition.

Procedure without setting a controller inhibit

1. Deactivate the auto DCB function with

C00019

= 0.

2. Do not activate the controller inhibit. Instead, stop the drive by selecting a setpoint of 0 or by

activating the quick stop function.

Initial commissioning steps

1. Set the motor selection/motor data

• When selecting and parameterising the motor, the motor nameplate data and the equivalent circuit

diagram data are relevant. Detailed information can be found in the "

Motor selection/Motor data

"

chapter.

( 82)

Depending on the motor manufacturer, proceed as follows:
Lenze motor:

Selecting a motor from the motor catalogue in the

»Engineer«

- or -

1.Set the motor nameplate data

2.

Automatic motor data identification

Third party manufacturer's motor:

1.Set the motor nameplate data

2.

Automatic motor data identification

or set known

equivalent circuit diagram manually:

C00084

: Motor stator resistance

C00085

: Motor stator leakage inductance

C00092

: Motor magnetising inductance

2. Determine the motor control:

C00006

= "4: SLVC: Vector control"

3. Set the slip compensation (

C00021

).

Slip compensation ( 154)