12 ls_analoginput, Ls_analoginput, 12 function library – Lenze 8400 motec User Manual
Page 477
Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05
477
12
Function library
12.12
LS_AnalogInput
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.12
LS_AnalogInput
The LS_AnalogInput system block displays the analog inputs in the application on I/O level.
Outputs
Related topics:
Identifier
Data type
Value/meaning
nIn1_a
| INT
Analog input 1
• Scaling:
±2
14
≡ ±10 V for use as voltage input
+2
14
≡ +20 mA for use as current input
bCurrentErrorIn1
BOOL
Status signal "Current input error"
• Only when analog input 1 is used as current input.
• Application: Cable-breakage monitoring of the 4 ...20 mA circuit.
TRUE |I
AIN1
| < 4 mA
nIn2_a
| INT
Analog input 2
• Scaling: ±2
14
≡ ±10 V
• Only available with Communication Unit E84DGFCXxNx (no fieldbus, extended
terminal design).