C00118 | dox inversion, C00122 | initial value motor overload (i·xt), C00120 – Lenze 8400 motec User Manual

Page 352: C00122, C00118, 11 parameter reference

Advertising
background image

11

Parameter reference

11.2

Parameter list | C00118

352

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00118

C00120

C00122

Parameter | Name:

C00118 | DOx inversion

Data type: UNSIGNED_8

Index: 24457

d

= 5F89

h

The polarity of each digital output of the device can be inverted via this bit field.
Setting range

(min. hex value | max. hex value)

Lenze setting

0x00

0xFF 0x00 (decimal: 0)

Value is bit-coded: (= bit set)

Info

Bit 0  Relay inverted

Relay inversion

Bit 1  DO1 inverted

Inversion of digital output 1

Bit 2  Reserved
Bit 3  Reserved
Bit 4  Reserved
Bit 5  Reserved
Bit 6  Reserved
Bit 7  Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C00120 | Setting of motor overload (I²xt; C0088/C0098)

Data type: INTEGER_16

Index: 24455

d

= 5F87

h

The Inverter Drives 8400 are provided with a simple, sensorless, thermal I²xt motor monitoring of self-ventilated

standard motors which is based on a mathematical model.

• For setting notes, see chapter "

Motor overload monitoring (I2xt)

".

• The response for triggering the monitoring can be selected in

C00606

.

• The current thermal motor load is displayed in

C00066

.

Setting range

(min. value | unit | max. value)

Lenze setting

0

%

250 100 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00122 | Initial value motor overload (I²xt)

Data type: UNSIGNED_16

Index: 24453

d

= 5F85

h

From version 04.01.00

The thermal motor load displayed in

C00066

is pre-initialised with the value set here when the device is connected

to the mains.

• If "100.00 %" is set, the last value at switching off the device is used for the initialisation.

• Recommended setting for operation according to UL: 50.00 %

Motor overload monitoring (I2xt)

Setting range

(min. value | unit | max. value)

0.00

%

100.00

Subcodes

Lenze setting

Info

C00122/1

0.00 %

Initial value motor overload (I²xt)

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Advertising