3commissioning – Lenze 8400 motec User Manual

Page 34

Advertising
background image

3

Commissioning

3.5

Commissioning of the "Actuating drive speed" technology application

34

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.5

Commissioning of the "Actuating drive speed" technology application

[3-1]

Block diagram for wiring the commissioning example for the "Actuating drive speed" application

Commissioning steps
Find a description of the commissioning steps of the "Actuating drive speed" technology application

below.
Please observe the sequence of the steps in the following chapters and follow them through

carefully. This will help you to commission your controller quickly and as safely as possible:

Prepare controller for commissioning

( 35)

Creating an »Engineer« project & going online

( 36)

Parameterising the motor control

( 37)

Parameterise application

( 39)

Saving parameter settings safe against mains failure

( 41)

Enabling controller and selecting speed

( 41)

Note!

Take all the necessary safety precautions before you carry out the following

commissioning steps and switch the device on!

Safety instructions with regard to commissioning

( 31)

System constellation

AR

Reference voltage (10 V) for analog signals

AU

Speed setpoint selection (slider of setpoint potentiometer R)

• Scaling: 10 V ≡ 100 % ≡ 1500 rpm

1

(for a 4-pole motor)

GND

Ground potential (GND) for analog signals

RFR

Controller enable

DIAG

Diagnostic interface for connecting the USB diagnostic adapter

8400 motec

X61

X6

DIAG

U V W

DO1 24O GND

NO COM AR

AU GND

X3/X4

RFR DI1 DI2 DI3 DI4 DI5 DO1 24O GND

NO COM

M

3~

i

R

1k

... 10k

W

W