Diagnostics & error management

9.8

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Sd3: Open circuit - feedback system [xx.0123.00205]

An01: AIN1_I < 4 mA [xx.0125.00001]

CE04: MCI communication error [xx.0127.00002]

Smr1: Module internal watchdog or trap [xx.0127.00003]

Smr2: Module offline - no status or PDOs [xx.0127.00004]

Response (Lenze setting printed in bold)

Setting:

C00586

( Adjustable response)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

• HTL encoder cable interrupted.

• HTL encoder is defective.

Note: May also be caused by a very dynamic acceleration

or starting up against a blocked motor shaft (e.g. with a

closed holding brake).

• Check HTL encoder cable.

• Check HTL encoder.

• Check related terminals.

• Switch off monitoring (

C00586

= "0: No reaction")

when the HTL encoder is not used.

Response (Lenze setting printed in bold)

Setting:

C00598/1

( Adjustable response)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Open-circuit monitoring for analog input 1 has tripped.

• Only if the analog input has been configured as a cur-

rent loop of 4 ... 20 mA (

C00034/1

= 2).

• Check wiring of the analog input terminals for open

circuit.

• Check minimum current values of the signal sources.

Response (Lenze setting printed in bold)

Setting:

C01501/1

( Adjustable response)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Communication error with communication unit

• Eliminate EMC interference.

• Mains switching or restart of the controller, respec-

tively.

• Exchange communication unit/drive unit.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Internal error Communication Unit

• Mains switching or restart of the controller, respec-

tively.

• Replace Communication Unit.

• Please contact Lenze if the problem occurs again.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

Communication Unit is offline

• Increase timeout in

C01503/1

.

• Mains switching or restart of the controller, respec-

tively.

• Check correct identification of the Communication

Unit in

C00203/3

.

• Replace Communication Unit.

• Please contact Lenze if the problem occurs again.