C00028 | ainx: input voltage, C00029 | ainx: input current, C00033 | ainx: output value – Lenze 8400 motec User Manual

Page 340: C00028/1, C00029/1, C00033/1, C00028/2, C00029/2, Ain1: inpu, 11 parameter reference

Advertising
background image

11

Parameter reference

11.2

Parameter list | C00028

340

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00028

C00029

C00033

Parameter | Name:

C00028 | AINx: Input voltage

Data type: INTEGER_16

Index: 24547

d

= 5FE3

h

Display of the input voltage at the analog inputs

Analog terminals

Display range

(min. value | unit | max. value)

-10.0

V

10.0

Subcodes

Info

C00028/1

AIN1: Input voltage

C00028/2

AIN2: Input voltage

From version 04.00.00

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00029 | AINx: Input current

Data type: INTEGER_16

Index: 24546

d

= 5FE2

h

Display of the Input current at the analog input

• When the analog input is configured for current measurement (

C00034/1

= 1 or 2).

• When

C00034/1

is set = 2 (4 ... 20 mA), 0 ... 16 mA is displayed.

Analog terminals

Display range

(min. value | unit | max. value)

0.0

mA

20.0

Subcodes

Info

C00029/1

AIN1: Input current

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00033 | AINx: Output value

Data type: INTEGER_16

Index: 24542

d

= 5FDE

h

Display of the output value in percent of the analog input amplifier

• 100 % ≡ 16384 ≡ +10 V / +20 mA

Analog terminals

Display range

(min. value | unit | max. value)

-199.9

%

199.9

Subcodes

Info

C00033/1

AIN1: Output value

C00033/2

AIN2: Output value

From version 04.00.00

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100