13 application examples – Lenze 8400 motec User Manual

Page 502

Advertising
background image

13

Application examples

13.1

Sequence control

502

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Special features:
In partial-load operational range, (e.g. during the night), it can be operated with a small unit and

thus energy can be saved.
For pump 2, both a second 8400 motec and a starter or contactor can be used.

[13-2] Level curve

Example parameter setting:

V

IN1

(pump 1) = 0 ... 50 %

V

IN2

(pump 2) = 0 % / 50 %

9

,1

287

9





9

,1

9

727$/

9

,1

287

9





9

,1

9

727$/

Parameter

Info

Setting

Info

Settings for motor control and device control

C00006

Motor control

8: VFCplus: V/f quadr

V/f characteristic control (VFCplus)

C00141

Auto-start option

0x01

Starting performance of the controller:

Inhibit after mains connection.

Auto-start option "Inhibit at power-

on"

C00019

Auto-DCB: Threshold

100 rpm

Automatic DC-injection braking (auto

DCB)

C00106

Auto-DCB: Hold time

0.0 s

DC-injection braking deactivated.

Assignment of the input/output terminals

C00007

Control mode

10:

Terminals 0

The pre-assignment is changed through

the following parameter setting.

C00621/1

LS_DigitalOutput:bRelay

220:

L_DigitalDelay_1

_bOut

The relay is triggered by the binary delay

element.

The relay causes pump 2 to be released

(delayed).

C00701/5

LA_NCtrl: bSetSpeedCcw

0: Not connected

Now, a reversal or rotation via digital in-

put DI4 is not possible anymore.

Analog input

Analog terminals

C00034

AINx: Configuration

2: 4...+20mA

Input signal is current signal

4 mA ... 20 mA.

C00598

Resp. to open circuit AINx

0: No Reaction

Open-circuit monitoring is deactivated.

Setpoint generator

L_NSet_1

C00012

Acceleration time - main setpoint

20 s

C00013

Deceleration time - main set-

point

20 s