Ou: dc bus overvoltage [xx.0123.00014, Lu: dc bus undervoltage [xx.0123.00015, Oc1: power section - short circuit [xx.0123.00016 – Lenze 8400 motec User Manual

Page 306: Ssage, Lu: dc-bus, Undervoltage, Xx.0123.00015, Xx.0123.00016, Xx.0123.00014, 9diagnostics & error management

Advertising
background image

9

Diagnostics & error management

9.8

Error messages of the operating system

306

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

oU: DC bus overvoltage [xx.0123.00014]

LU: DC bus undervoltage [xx.0123.00015]

oC1: Power section - short circuit [xx.0123.00016]

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

The device has detected an overvoltage in the DC bus. To

protect the device hardware, the inverter control is

switched off.

• Depending on the configuration of the auto-start lock

function, set

C00142

so that, when this error is

tripped, the controller only restarts after the control-

ler inhibit has been switched.

• If this error message remains active longer than the

time set in

C00601

, a "Fault" is tripped.

• Reduce load in generator mode.

• Use a brake resistor.

• Use a regenerative power supply unit.

• Establish a DC-bus connection.

Response (Lenze setting printed in bold)

Setting:

C00600/1

( Adjustable response)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

The device has detected a DC bus undervoltage. The in-

verter control is switched off because the drive proper-

ties of the motor control cannot be provided anymore

due to the DC bus undervoltage.

• Depending on the configuration of the auto-start lock

function, set

C00142

so that, when this error is

tripped, the controller only restarts after the control-

ler inhibit has been switched.

• Switch on mains supply or ensure sufficient supply via

DC bus.

• Adjust setting in

C00142

if required.

Response (Lenze setting printed in bold)

No Reaction  Fault  Trouble  WarningLocked

Cause

Remedy

The device has recognised a short circuit of the motor

phases. To protect the device electronics, the inverter

control is switched off.

• Mostly, incorrectly executed motor connections are

the cause.

• If the device is inappropriately dimensioned with re-

gard to the motor load and the current limitation in

the controller (Imax controller) is set incorrectly, this

error message may also occur.

Motor control: Defining current limits

• Check motor connections and the corresponding plug

connector on the device.

• Only use permissible combinations of device power

and motor power.

• Do not set the dynamics of the current limitation con-

troller too high.