5

Motor control (MCTRL)

5.14

Monitoring

178

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

The monitoring function calculates the braking current I

Br

from the current DC-bus voltage U

DC_act

and the brake resistance parameterised in

C00129

:

• The calculation considers the thermal utilisation of the brake resistor based on the following

parameters:

• Resistance value (

C00129

)

• Continuous power (

C00130

)

• Thermal capacity (

C00131

)

• In the Lenze setting these parameters are preset with the corresponding power-adapted Lenze

brake resistor.

C00133

indicates the calculated utilisation of the brake resistor in [%].

• A utilisation of 100 % corresponds to the continuous power of the brake resistor depending

on the maximally permissible temperature limit.

Related topics:

Braking operation/brake energy management

( 163)

Note!

The monitoring function can also be triggered due to a value entered in

C00129

although a brake resistor is not even connected.

I

Br

U

DC_act

C00129

--------------------

=