3commissioning – Lenze 8400 motec User Manual

Page 40

Advertising
background image

3

Commissioning

3.5

Commissioning of the "Actuating drive speed" technology application

40

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4. Adapt the application parameters:

Tip!

• Click the Signal flow button to go down one dialog level to the signal flow of the

application with further possible parameter settings. See chapter "

Basic signal flow

".

( 202)

• The preconfigured I/O connection in the selected control mode can be changed via

configuration parameters. See chapter "

User-defined terminal assignment

".

( 191)

More detailed informaton on the technology application:

TA "Actuating drive speed"

( 201)

Interface description

( 206)

wDriveControl control word

( 211)

Terminal assignment of the control modes

( 214)

Setting parameters (short overview)

( 219)

Pre-assignment of the application

( 220)

Parameter

Lenze setting

Info

Value Unit

Accel. time - main setpoint

(

C00012)

2.0 s

The setpoint is led via a ramp function generator with

linear characteristic. The ramp function generator

converts setpoint step-changes at the input into a ramp.

L_NSet_1 ( 443)

Decel. time - main setpoint

(

C00013

)

2.0 s

Reference speed

(

C00011

)

1500 rpm

All speed setpoint selections are provided in % and

always refer to the reference speed set in

C00011

.

The motor reference speed is indicated on the motor

nameplate.

Decel. time - quick stop

(

C00105

)

5.0 s

If quick stop is requested, motor control is decoupled

from the setpoint selection and, within the deceleration

time parameterised in

C00105

, the motor is brought to

a standstill (n

act

= 0).

Activate/deactivate quick stop ( 65)

Fixed setpoint 1

(

C00039/1

)

40.0 %

A fixed setpoint for the setpoint generator can be

activated instead of the main setpoint via the selection

inputs bJogSpeed1 and bJogSpeed2.

• Fixed setpoints are selected in [%] based on the

reference speed (

C00011

).

L_NSet_1 ( 443)

Fixed setpoint 2

(

C00039/2

)

60.0 %

Fixed setpoint 3

(

C00039/3

)

80.0 %

Advertising