C00598 | resp. to open circuit ainx, C00600 | resp. to dc bus undervoltage, C00601 | del. resp.to fault: dc bus overvoltage – Lenze 8400 motec User Manual

Page 386: C00600/1, Igger in, C00601/1, Has elapsed (if, C00598/1, C00601, 11 parameter reference

Advertising
background image

11

Parameter reference

11.2

Parameter list | C00598

386

Lenze · 8400 motec · Reference manual · DMS 4.1 EN · 08/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00598

C00600

C00601

Parameter | Name:

C00598 | Resp. to open circuit AINx

Data type: UNSIGNED_8

Index: 23977

d

= 5DA9

h

Configuration of monitoring the analog input

Analog terminals

Selection list

0 No Reaction
1 Fault
2 Trouble
4 WarningLocked

Subcodes

Lenze setting

Info

C00598/1

1: Fault

Response to open circuit at AIN1 if configured as

4 ... 20 mA current loop

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00600 | Resp. to DC bus undervoltage

Data type: UNSIGNED_8

Index: 23975

d

= 5DA7

h

Configuration of monitoring of the motor control (group 3)
Selection list

1 Fault
2 Trouble

Subcodes

Lenze setting

Info

C00600/1

2: Trouble

Response to DC bus undervoltage

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00601 | Del. resp.to fault: DC bus overvoltage

Data type: UNSIGNED_16

Index: 23974

d

= 5DA6

h

Error response delay times
Setting range

(min. value | unit | max. value)

0.00

s

65.00

Subcodes

Lenze setting

Info

C00601/1

2.00 s

Delay time for triggering the "DC-bus overvoltage" error

• If a DC-bus overvoltage occurs, an error will not be

triggered until the set delay time has elapsed.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000