Motor control (MCTRL)

5.10

Parameterisable additional functions

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.10.3.1

Manual DC-injection braking (DCB)

DC-injection braking can be manually activated via the bSetDCBrake process input.

• For HIGH-active inputs, DC-injection braking is active as long as the signal is at HIGH level.
• After the hold time (

C00107

) has expired, the controller sets the pulse inhibit (CINH).

Tip!

• In the preset "Terminals 0" control mode, DC-injection braking can be manually

activated via the digital input DI3.

• In the preset "Terminals 11" control mode, DC-injection braking can be manually

activated via the digital input DI2.

5.10.3.2

Automatic DC-injection braking (auto DCB)

"Automatic DC-injection braking" (referred to in the following as "auto DCB") can be used if there is
a requirement that the drive be isolated from the supply at n

0.

Note!

Deactivate automatic DC-injection braking when a holding brake is used!

• For this purpose, go to

C00019

and set the auto DCB threshold to "0".

• Background: Controller inhibit is already activated by the

Holding brake control

.

( 268)

Up to and including version 03.xx.xx

, DC-injection braking is activated immediately.

From version 04.00.00

and before DC-injection braking is activated

• and device smaller than 3 kW, it is always waited 250 ms and
• with devices bigger than 3 kW, it is always waited 1 s.

From version 05.00.00

, the waiting time before activating DC-injection braking can be

deactivated. If bit 8 is set in

C00143

and the auto-DCB threshold is ≤ 5 Hz, the DC-

injection braking is activated immediately if the value falls below the threshold (without

above-mentioned waiting time).

C00019

[rpm] = auto DCB threshold [Hz] * 60 / number of pole pairs