Commissioning

3.5

Commissioning of the "Actuating drive speed" technology application

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3.5.3

Parameterising the motor control

1. Select the Application parameters tab from the Workspace.

• The motor control parameters, among other things, can be found on the left:

2. In the Motor control list field (

C00006

), select the desired motor control.

3. Adapt the motor control parameters:

Note!

In the Lenze setting, the V/f characteristic control (VFCplus) with linear characteristic is

set in

C00006

as motor control.

• V/f characteristic control (VFCplus) is a motor control mode for classic frequency

inverter applications on the basis of a simple and robust control procedure for the

operation of machines with a linear or quadratic load torque characteristic (e.g. fans).

• The presettings of the parameters ensure that the controller is immediately ready for

operation and the motors works adequately without further parameterisation if a

controller and a 50 Hz asynchronous machine with matching performances are

assigned.

Parameter

Lenze setting

Info

Value Unit

V/f base frequency

(

C00015)

50.0 Hz

Adapting the V/f base frequency ( 101)

Imax in motor mode

(

C00022

)

47.00 A

Optimising the Imax controller ( 103)

Vmin boost

(

C00016

)

0.0 %

Adapting the Vmin boost ( 102)