Diagnostics & error management

9.6

Monitoring

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.6.2

Setting the error response

When a monitoring function responds, the response set for this monitoring function (Trouble, Fault,

etc.) will be triggered.

• For many monitoring functions the response can be individually parameterised via parameters.

Tip!
The table in the chapter entitled "

Short overview (A-Z)

" contains the error messages for

which the response can be set.

( 302)

Warning thresholds
Some of the monitoring functions are activated if a defined warning threshold has been exceeded.

• The corresponding preset threshold values can be changed via the following parameters:

Parameter

Info

Lenze setting

Value Unit

C00120

Motor overload threshold (I²xt)

100 %

C00123

Device utilisat. threshold (Ixt)

100 %

C00909/1

Max. positive speed

120 %

C00909/2

Max. negative speed

120 %

C00910/1

Max. positive output frequency

300 Hz

C00910/2

Max. negative output frequency

300 Hz